Thyristors are typically used as phase-controlled current valves for AC to DC conversion and vice versa, operating at low frequencies (most often around AC line frequency). In the conducting state, thyristors feature very low losses, making them attractive devices to efficiently control very high currents and energies.


All ABB thyristors are press-pack devices. They are pressed with a relatively high force onto heat-sinks which also serve as electrical contacts to the thyristor terminals.

Part Number VDRM(V) ITAV(A) ITSM(kA) Package*

(mm)

5STP 06T1600 1600 641 9.9 52.5/29.5
5STP 10D1601 1600 969 15.0 58.5/34
5STP 10T1600 1600 969 15.0 58.5/34
5STP 20F1601 1600 1901 27.3 74.5/47
5STP 20T1600 1600 1956 27.3 74.5/47
5STP 34H1601 1600 3370 49.0 101.5/63
5STP 34T1600 1600 3370 49.0 101.5/63
5STP 07D1800 1800 730 9.0 58.5/34
5STP 09D1801 1800 932 13.7 58.5/34
5STP 18F1800 1800 1660 21.0 74.5/47
5STP 18F1801 1800 1825 26.2 74.5/47
5STP 18T1800 1800 1870 26.2 74.5/47
5STP 30H1801 1800 3108 47.0 102/63
5STP 42L1800 1800 4390 64.0 120/78
5STP 30T1800 1800 3108 47.0 101.5/63
5STP 50Q1800 1800 6100 94.0 150/100
5STP 09D2201 2200 863 12.0 58.5/34
5STP 17F2201 2200 1702 25.5 74.5/47
5STP 17T2200 2200 1743 25.5 74.5/47
5STP 29H2201 2200 2855 45.0 101.5/63
5STP 29T2200 2200 2855 45.0 101.5/63
5STP 06D2800 2800 620 8.8 60/34
5STP 08T2800 2800 792 10.6 58.5/34
5STP 08D2801 2800 792 10.6 58.5/34
5STP 15T2800 2800 1589 23.6 74.5/47
5STP 16F2800 2800 1400 18.0 74.5/47
5STP 16F2801 2800 1554 23.6 74.5/47
5STP 27H2801 2800 2670 43.0 101.5/63
5STP 27T2800 2800 2670 43.0 101.5/63
5STP 33L2800 2800 3740 65.5 120/78
5STP 45N2800 2800 5080 77.0 150/100
5STP 45Q2800 2800 5490 77.0 150/100
5STP 04D4200 4200 470 7.1 60/34
5STP 12F4200 4200 1150 17.3 75/47
5STP 21H4200 4200 2192 32.0 101.5/63
5STP 28L4200 4200 3170 54.0 120/78
5STP 38N4200 4200 3960 64.5 150/100
5STP 38Q4200 4200 4275 64.5 150/100
5STP 04D5200 5200 440 6.1 60/34
5STP 17H5200 5200 1975 34.0 102/63
5STP 25L5200 5200 2760 50.5 120/78
5STP 25M5200 5200 2540 50.5 120/78
5STP 34N5200 5200 3600 63.0 150/100
5STP 34Q5200 5200 3875 63.0 150/100
5STP 52U5200 5200 5120 99.0 172/110
5STP 03X6500 6500 350 4.7 60/34
5STP 03D6500 6500 380 4.7 60/34
5STP 08F6500 6500 830 15.1 75/47
5STP 08G6500 6500 720 15.1 75/47
5STP 12K6500 6500 1370 31.5 102/63
5STP 18M6500 6500 1800 47.5 120/78
5STP 26N6500 6500 2810 65.0 150/100
5STP 42U6500 6500 4250 86.0 172/110
5STP 48Y7200 7200 4840 92.0 192/138
5STP 45Y8500 8500 4240 90.0 192/138